Aggressive Cooling Water Candidates Comparison Chart

thumbnail of Aggressive Cooling Water Candidates

SEA-CURE®

Comparative Properties for Aggressive Cooling Water Candidates

 

Property SEA-CURE® Ti Grade 2 90-10 Cu/Ni AL6XN®
Ultimate Strength* 586 MPa 345 MPa 276 MPa 689 MPa
Yield Strength* 478 MPa 276 MPa 103 MPa 310 MPa
Elongation* 20% 20% 25% 30%
Rockwell Hardness** Rc 25 Rb 92 Rb 20 Rb 100
Modulus of Elasticity 2.17 x 10^5 1.06 x 10^5*** 1.24 x 10^5 1.94 x 10^5
Density (kg/m^3) 7.695 4.429 8.858 8.027
Thermal Expansion
(mm/mm-°C)
9.68 9.4 17.1 15.7
Thermal Conductivity
(watts/m-°K)
17.1 21.6 45.0 13.7
Fatigue Endurance 241 MPa 110 MPa 172 MPa 227 MPa

* Minimum ASTM Value
** Maximum ASTM Value
*** Average of Longitudinal and Transverse

More SEA-CURE® information is available at www.seacuresolutions.com.